|
ARTICLE 1733
International Property Maintenance Code
1733.01 Adoption.
1733.02 Additions, Deletions, and Modifications.
CROSS REFERENCE
Adoption by reference - See 3rd Class Charter Law 608(a)
(53 P.S. 41608(a); 3rd Class 2403(67) (53 P.S. 37403(67)
1733.01 ADOPTION
There is hereby adopted the 2009 International Property Maintenance
Code with deletions and amendments thereto as hereinafter noted.
1733.01 ADDITIONS, DELETIONS, AND MODIFICATIONS.
The following articles, representing revisions or additions to
the 2009 ICC International Property Maintenance Code shall be applicable
for the purpose of this Ordinance:
CHAPTER 1 ADMINISTRATION
SECTION 106 VIOLATIONS
That Sub-section PM-106.4 titled Violation Penalties which reads
as follows:
Any person who shall violate a provision of this code, or fail
to comply therewith, or with any of the requirements thereof, shall
be prosecuted within the limits provided by state or local laws.
Each day that a violation continues after due notice has been served
shall be deemed a separate offense.
Be amended to read as follows:
106.4 Penalty
Any person who shall violate a provision of this Ordinance or shall
fail to comply with any of the requirements thereof, or shall be
in violation of an approved plan or directive of the Inspector or
of a permit issued under the provisions of the Ordinance shall,
upon conviction thereof before the District Magistrate of the City
of Bethlehem, Pennsylvania, be liable to pay the following penalties:
a) First Violation – A fine of $200.00, or thirty (30) days
imprisonment, or both;
b) Second Violation – A fine of $500.00, or sixty days imprisonment,
or both;
c) Third and each subsequent violation – A fine of $1,000.00,
or ninety days imprisonment, or both.
Each day that a violation continues shall be deemed a separate
offense
SECTION 107 NOTICES AND ORDERS
That Sub-section 107.7 be added to read as follows:
107.7 ABSENTEE LANDLORD
No Certificate of Occupancy shall be issued for any rental dwelling,
excluding a dormitory and hotel (as defined in Article 2, PM-201.0
APPLIED MEANING OF WORD AND TERMS), unless there is provided to
the Inspection Bureau the name and address of an agent residing
within a twenty mile radius of the City of Bethlehem,authorized
to accept service of process on behalf of the title owner or operator
of said dwelling.
The authorization shall be signed by the agent designated to accept
service and the landlord or operator shall be required to contact
the Housing Bureau each year and/or upon the change of agency in
order to update the City records with regard to the name, address
and telephone number of the locally designated agent.
Failure to provide the information on the designated local agent,
after two (2) weeks notice, will result in the revocation of the
Certificate of Occupancy and the closure of the property to renters
until a new and valid Certificate of Occupancy is issued.
SECTION 108 UNSAFE STRUCTURES AND EQUIPMENT
That Sub-section 108.1.5(4) be deleted
That Sub-section 108.6 titled Abatement methods that reads as follows:
The owner, operator or occupant of a building, premises or equipment
deemed unsafe by the code official shall abate or cause to be abated
or corrected such unsafe conditions either by repair, rehabilitation,
demolition or other approved corrective action
Be amended to read as follows:
The owner or operator of a building, premises or equipment deemed
unsafe by the code official shall abate or cause to be abated or
corrected such unsafe conditions either by repair, rehabilitation,
demolition or other approved corrective action
SECTION 110 DEMOLITION
That Sub-section 110.1 titled General that reads as follows:
The code official shall order the owner of any premises upon which
is located any structure, which in the code official judgment after
review is so deteriorated or dilapidated or has become so out of
repair as to be dangerous, unsafe, insanitary or otherwise unfit
for human habitation or occupancy, and such that is it unreasonable
to repair the structure, to demolish and remove such structure;
or if such structure is capable of being made safe by repairs, to
repair and make safe and sanitary, or to board up and hold for future
repair or to demolish and remove at the owner’s option; or
where there has been a cessation of normal construction of any structure
for a period of more than two years, the code official shall order
the owner to demolish and remove such structure, or board up until
future repair. Boarding the building up for future repair shall
not extend beyond one year, unless approved by the building official.
Be amended to read as follows:
The code official shall order the owner of any premises upon which
is located any structure, which in the code official judgment after
review is so deteriorated or dilapidated or has become so out of
repair as to be dangerous, unsafe, unsanitary or otherwise unfit
for human habitation or occupancy, and such that is it unreasonable
to repair the structure, to demolish and remove such structure;
or if such structure is capable of being made safe by repairs, to
repair and make safe and sanitary, or to board up and hold for future
repair or to demolish and remove at the owner’s option; or
where there has been a cessation of normal construction of any structure
for a period of more than two years, the code official shall order
the owner to demolish and remove such structure, or board up until
future repair. Boarding the building up for future repair shall
not extend beyond sixty days, unless approved by the building official.
CHAPTER 3 GENERAL REQUIREMENTS
SECTION 302 EXTERIOR PROPERTY AREAS
That Sub-section 302.4 titled Weeds which reads as follows:
All premises and exterior property shall be maintained free from
weeds or plant growth in excess of (jurisdiction to insert height
in inches). All noxious weeds shall be prohibited. Weeds shall be
defined as all grasses, annual plants and vegetation, other than
trees or shrubs provided; however, this term shall not include cultivated
flowers and gardens.
Be amended to read as follows:
All premises and exterior property shall be maintained free from
weeds or plant growth in excess of 12”. All noxious weeds
shall be prohibited. Weeds shall be defined as all grasses, annual
plants and vegetation, other than trees or shrubs provided; however,
this term shall not include cultivated flowers and gardens.
That Sub-section 302.8 titled Motor Vehicles which reads as follows:
Except as provided for in other regulations, no inoperative or
unlicensed motor vehicle shall be parked, kept or stored on any
premises, and no vehicle shall at any time be in a state of major
disassembly, disrepair, or in the process of being stripped or dismantled.
Painting of vehicles is prohibited unless conducted inside an approved
spray booth.
Exception: A vehicle of any type is permitted to undergo major
overhaul, including body work, provided that such work is performed
inside a structure or similarly enclosed area designed and approved
for such purposes.
Be amended to read as follows:
(A) No person shall abandon and/or store any unregistered vehicle
on private property within the City of Bethlehem. No vehicle at
any time be in a state of major disassembly, disrepair or in the
process of being stripped or dismantled. Painting of vehicles is
prohibited unless conducted inside an approved spray booth.
(1) A vehicle, other than a pedalcycle, shall be presumed to be
abandoned under one or more of the following circumstances, but
the presumption is rebuttable by a preponderance of the evidence:
(i) The vehicle is physically inoperable and is left unattended
on private property for more than 48 hours.
(ii) The vehicle has remained illegally on private property for
more than 48 hours.
(iii) The vehicle is left unattended on private property for more
than 48 hours and does not bear the following:
(a) A valid registration plate.
(b) A current certificate of inspection.
(c) An ascertainable vehicle identification number.
Exception: A vehicle of any type is permitted to undergo major
overhaul, including body work provided that such work is performed
inside a structure or similarly enclosed area designed and approved
for such purpose, that is an accessory use, incidental to the dwelling
as defined in Article 1302.02 of the City of Bethlehem Zoning Ordinance
#2210. All wrecked car parts and similar unused components of a
junk vehicle must not be stored on any private property in clear
view of the public right of way.
(B) A vehicle shall be deemed to be abandoned when it remains on
private property for more than (48) hours and any of the following
conditions apply:
(1) The vehicle is physically inoperable.
(2) The vehicle is left unattended.
(3) The vehicle does not have a valid
registration plate.
(4) The vehicle does not have a current
certificate of inspection.
(5) The Vehicle Identification Number(VIN)is
not ascertainable.
(6) The vehicle remains without the consent of
the owner or person in charge of the property.
(C) If the owner of an abandoned and/or junked motor vehicle cannot
be located or does not remove the vehicle, the code official shall
contact the Bethlehem Police Department, who is authorized to remove
said vehicle under Transportation 67 PA Code Chapter 253 titled
Salvors and Vehicles Title 75 Chapter 73 of the Abandoned Vehicles
and Cargos Code of the Commonwealth of PA.
(D) Any vehicle undergoing major overhaul, including body work,
shall be registered to the owner of the property where such work
is being done or registered to the lawful resident/tenant of the
property where the work is being done.
SECTION 304 EXTERIOR STRUCTURE
Sub-section 304.1.1 Unsafe Conditions
That Sub-section 304.1.1(1) be deleted
That Sub-section 304.1.1(2) be deleted
That Sub-section 304.1.1(3) be deleted
That Sub-section 304.1.1(6) be deleted
That Sub-section 304.1.1(7) be deleted
That Sub-section 304.1.1(10) be deleted
Sub-section 304.3 Premises Identification
That Sub-section 304.3.1 be added to read as follows:
All existing properties with a thoroughfare of public access to
the back of the property be identified with approved address numbers
placed in a position to be plainly legible and visible from the
thoroughfare running behind the property. This may require the address
numbers be attached to a garage, shed, fence, retaining wall and
any other similar structure. The numbers shall contrast with the
background. Address numbers shall be Arabic numerals or alphabet
letters. Numbers shall be a minimum of 4 inches high with a minimum
stroke width of 0.5 inches.
That Sub-section 304.14 titled Insect Screens which reads as follows:
During the period from [DATE] to [DATE], every door, window and
other outside opening required for ventilation of habitable rooms,
food preparation areas, food service areas or any areas where products
to be included or utilized in food for human consumption are processed,
manufactured, packaged or stored, shall be supplied with approved
tightly fitting screens of not less than 16 mesh per inch (16 mesh
per 25 mm) and every swinging door shall have a self closing device
in good working condition.
Exception: Screens shall not be required where other approved means,
such as air curtains or insect repellent fans are employed.
Be amended to read as follows:
Every exterior window and door frame that has the necessary mechanical
storm and screen hardware in place, must be provided with proper
fitting windows and screens.
Delete the following exception:
Screens shall not be required where other approved means, such
as air curtains or insect repellant fans are employed.
That Sub-section 304.19 titled Boarded up windows be added to read
as follows:
No exterior window, skylight or door frame of any structure facing
toward or visible from the public right of way shall be covered
with plywood or other non-approved materials longer than 60 days.
After 60 days, all temporary cover over exterior windows, skylights
and doors that face toward or are visible from the public right
of way, shall be removed, and the exterior windows, skylights and
doors shall be restored.
Restoration of exterior windows, skylights and doors must include
proper fitting windows and door frames, hardware, locks and glazing
and be maintained in proper working condition.
All exposed exterior metal or wood surfaces shall be protected
from the elements and against decay or rust by periodic application
of weatherproofing/coating material.
SECTION 305 INTERIOR STRUCTURE
Sub-section 305.1.1 Unsafe Conditions
That Sub-section 305.1.1(1) be deleted
That Sub-section 305.1.1(2) be deleted
That Sub-section 305.1.1(3) be deleted
That Sub-section 305.1.1(4) be deleted
That Sub-section 305.1.1(6) be deleted
SECTION 306 COMPONENT SERVICEABILITY
Sub-section 306.1.1 Unsafe Conditions
That Sub-section 306.1.1(1) be deleted
That Section 308.4 titled Furniture be added to read as follows:
All furniture, materials and other similar products designed, built,
and manufactured exclusively for indoor living use shall not be
placed or stored on exterior porches, in yards or any part of an
exterior property in residential and non-residential areas. The
storage or placement of automobile car seats and other non-weather
resistant materials shall also be prohibited. Any person who fails
to comply with this Section after forty-eight hours notice from
the City to do so, shall be guilty of violating the provisions of
this Section and shall be subject to the fines set forth in Article
1733 Section PM 106.4
SECTION 309 PEST ELIMINATION
Sub-section 309.1 Infestation
That Sub-section 309.1.2 be added to read as follows:
All extermination must be administered by a state certified technician
CHAPTER 4 LIGHT, VENTILATION AND OCCUPANCY LIMITATIONS
SECTION 402 LIGHT
Sub-section 402.2 titled Common halls and stairways which reads
as follows:
Every common hall and stairway in residential occupancies, other
than in one- and two- family dwellings, shall be lighted at all
times with at least a 60-watt standard incandescent light bulb for
each 200 square feet (19 m?) of floor area or equivalent illumination,
provided that the spacing between lights shall not be greater than
30 feet (9144 mm). In other than residential occupancies, means
of egress, including exterior means of egress stairways shall be
illuminated at all times the building space served by the means
of egress is occupied with a minimum of 1 footcandle (11 lux) at
floors, landings and treads.
Be amended to read as follows:
Every common hall and stairway, other than in a one family dwelling,
shall be lighted at all times with at least a 60-watt standard incandescent
light bulb or equivalent for each 200 square feet of floor area,
provided that the spacing between lights shall not be greater than
30 feet. Every exterior stairway shall be illuminated with a minimum
of a 60 watt bulb at floors, landings and treads. Placement of larger
wattage light bulbs or additional rated light fixtures in the interior
or exterior shall be at the discretion of the Code Official.
SECTION 404 OCCUPANCY LIMITATIONS
Sub-section 404.4.1 titled Room area which reads as follows:
Every living room shall contain at least 120 square fee (11.2m²)
and every bedroom shall contain at least 70 square feet (6.5m²).
Be amended to read as follows:
Every living room shall contain at least 120 square feet (11.2
m²) and every bedroom occupied by one person shall contain
at least 70 square feet (6.5 m²) of floor area, and every bedroom
occupied by more than one person shall contain at least 50 square
feet (4.6 m²) of floor area for each occupant thereof. (see
Table)
MINIMUM AREA REQUIREMENTS
MINIMUM AREA IN SQUARE FEET
SPACE 1-2 OCCUPANTS 3-5 OCCUPANTS 6 OR MORE OCCUPANTS
Living Room No requirements 120 150
Dining Room No requirements 80 100
Bedrooms Shall comply with Section 404.4
Sub-section 404.7 titled Food Preparation be deleted in its entirety
CHAPTER 5 PLUMBING FACILITIES AND FIXTURE REQUIREMENTS
SECTION 506 SANITARY DRAINAGE SYSTEM
That Sub-section 505.4 titled Water heating facilities that reads
as follows:
Water heating facilities shall be properly installed, maintained
and capable of providing an adequate amount of water to be drawn
at every required sink, lavatory, bathtub, shower and laundry facility
at a temperature of not less than 110?F (43?C). A gas-burning water
heater shall not be located in any bathroom, toilet room, bedroom
or other occupied room normally kept closed, unless adequate combustion
air is provided. An approved combination temperature and pressure-relief
valve and relief valve discharge pipe shall be properly installed
and maintained on water heaters.
Be amended to read as follows:
Water heating facilities shall be properly installed, maintained
and capable of providing an adequate amount of water to be drawn
at every required sink, lavatory, bathtub, shower and laundry facility
at a temperature of not less than 110?F (43?C) and a maximum of
120?F. A gas-burning water heater shall not be located in any bathroom,
toilet room, bedroom or other occupied room normally kept closed,
unless adequate combustion air is provided. An approved combination
temperature and pressure-relief valve and relief valve discharge
pipe shall be properly installed and maintained on water heaters.
Sub-section 506.3 titled Grease Interceptors be deleted in its
entirety.
CHAPTER 6 MECHANICAL AND ELECTRICAL REQUIREMENTS
SECTION 602 HEATING FACILITIES
That Sub-section 602.1 titled Facilities required which reads as
follows:
Heating facilities shall be provided in structure as required
by this section.
Be amended to read as follows:
All dwelling units shall have permanently installed, non-portable
type central heating facilities or fixed electrical heating systems
that are approved for the purpose and location where installed.
Heating facilities shall be capable of maintaining the required
temperatures in all habitable areas of the dwelling unit.
NOTE: Pipeless and/or ductless heating systems do not meet the
requirements of section PM-602.0.
Exception to read: At the discretion of the Code Official, pipeless
and/or ductless heating systems will be allowed providing said system
shall be capable of maintaining the required temperatures in all
habitable areas of the dwelling unit.
That Sub-section 602.3 titled Heat supply which reads as follows:
Every owner and operator of any building who rents, leases or lets
one or more dwelling unit, rooming unit, dormitory or guestroom
on terms, either expressed or implied, to furnish heat to the occupants
thereof shall supply heat during the period from [DATE] to [DATE]
to maintain a temperature of not less than 68?F (20?C) in all habitable
rooms, bathrooms, and toilet rooms.
Exceptions:
1. When the outdoor temperature is below the winter outdoor design
temperature for the locality, maintenance of the minimum room temperature
shall not be required provided that the heating system is operating
at its full design capacity. The winter outdoor design temperature
for the locality shall be as indicated in Appendix D of the International
Plumbing Code.
2. In areas where the average monthly temperature is above 30?F
(-1?C) a minimum temperature of 65?F (18?C) shall be maintained.
Be amended to read as follows:
Every owner and operator of any building who rents, leases or lets
one or more dwelling unit, rooming unit, dormitory or guestroom
shall furnish heat to the occupants thereof shall supply heat during
the period from [October 1] to [May 15] to maintain a temperature
of not less than 68?F (20?C) in all habitable rooms, bathrooms,
and toilet rooms.
Exceptions:
3. When the outdoor temperature is below the winter outdoor design
temperature for the locality, maintenance of the minimum room temperature
shall not be required provided that the heating system is operating
at its full design capacity. The winter outdoor design temperature
for the locality shall be as indicated in Appendix D of the International
Plumbing Code.
4. In areas where the average monthly temperature is above 30?F
(-1?C) a minimum temperature of 65?F (18?C) shall be maintained.
That Sub-Section 602.4 titled Occupiable work spaces which reads
as follows:
Indoor occupiable work spaces shall be supplied with heat during
the period from [DATE] to [DATE] to maintain a temperature of not
less than 65?F (18?C) during the period the spaces are occupied.
Exceptions:
1. Processing, storage and operation areas that require cooling
or special temperature conditions.
2. Areas in which persons are primarily engaged in vigorous physical
activities.
Be amended to read:
Indoor occupiable work spaces shall be supplied with heat during
the period from [October 1] to [May 15] to maintain a temperature
of not less than 65?F (18?C) during the period the spaces are occupied.
Exceptions:
1. Processing, storage and operation areas that require cooling
or special temperature conditions.
2. Areas in which persons are primarily engaged in vigorous physical
activities.
SECTION 604 ELECTRICAL FACILITIES
That Sub-section 604.2 titled Service that reads as follows:
The size and usage of appliances and equipment shall serve as a
basis for determining the need for additional facilities in accordance
with the ICC Electrical Code. Dwelling units shall be served by
a three-wire, 120/240 volt, single-phase electrical service having
a rating of not less than 60 amperes.
Be amended to read:
Every single family dwelling and housing rental unit shall be served
by a main that is not less than 100 amperes. Inadequate services
must be upgraded to meet the requirements of the National Electrical
Code.
Sub-section 604.3.1 titled Abatement of electrical hazards associated
with water exposure be deleted in its entirety.
Sub-section 604.3.1.1 be deleted
Sub-section 604.3.2 titled Abatement of electrical hazards associated
with fire exposure be deleted in its entirety.
Sub-section 604.3.2.1 titled Electrical equipment be deleted in
its entirety.
SECTION 605 ELECTRICAL EQUIPMENT
That Sub-section 605.2 titled Receptacles which reads as follows:
Every habitable space in a dwelling shall contain at least two
separate and remote receptacle outlets. Every laundry area shall
contain at least one grounded-type receptacle or a receptacle with
a ground fault circuit interrupter. Every bathroom shall contain
at least one receptacle. Any new bathroom receptacle outlet shall
have ground fault circuit interrupter protection.
Be amended to read:
Every habitable space in a dwelling shall contain at least two
separate and remote receptacle outlets. Every laundry area shall
contain at least one grounded type receptacle. Every bathroom and
powder room shall contain at least one (1) 3 wire 15 or 20 amp GFI
(Ground Fault Interrupter) and all outlets on light fixtures and
bathroom cabinets must be disconnected if not GFI protected.
That Sub-section 605.2.1 be added to read as follows:
a. All existing wall type receptacles which serve kitchen counter
top surfaces must be 3 wired 15 or 20 amp GFI (ground fault interrupted)
protected. Counter top spaces separated by range tops, refrigerators
and sinks shall be considered as separate counter top spaces and
apply to the requirements of this section.
b. All kitchen areas shall have (2) accessible 15 or 20 amp GFI
(ground fault interrupted) receptacle to serve counter top surfaces.
If no counter top is available, there shall be (2) accessible GFI
(ground fault interrupted) receptacles
at counter top height. Refrigerator receptacles shall not be counted
in determining GFI (ground fault interrupted) receptacle required
in the kitchen areas.
c. All existing receptacles located within 6' on either side of
an auxiliary sink shall be 3 wired 15 or 20 amp GFI (ground fault
interrupted).
d. All exterior receptacles must be 3 wired 15 or 20 amp G.F.I.
Ground Fault Interrupter) protected in weatherproof boxes and covers.
Exception: to read, All GFI outlets built into exterior walls must
have damp proof covers.
e. All electrical receptacles that cannot be tested for improper
wiring, installation, deterioration or damage due to immovable furniture,
appliances, or other obstructions shall be the responsibility of
the owner and/or the agent.
NOTE: The inspection of electrical panels and boxes is limited
to a visible inspection only.
Add new Sub-section 605.2.2 titled Common Area Branch Circuits
to read as follows:
Branch circuits in dwelling units shall supply only loads within
that dwelling unit or loads associated only with that dwelling unit.
Branch circuits required for purpose of lighting, central alarm,
signal communications or other needs for public or common areas
of a two family or multi-family dwelling shall not be supplied from
equipment that supplies an individual dwelling unit.
Add new Sub-section 605.2.3 titled Occupant to Have Ready Access
to read as follows:
Each occupant of a dwelling unit shall have ready access to all
overcurrent devices protecting the conductors supplying that occupancy.
CHAPTER 7 FIRE SAFETY REQUIREMENTS
Add new Sub-section 705 titled Carbon Monoxide Detectors to read
as follows:
SECTION 705 CARBON MONOXIDE DETECTION
705.1 General. An approved carbon monoxide (CO) detector shall
be installed, per the requirements of this Section, in all dwelling
units when a fossil fuel or solid fuel appliance is maintained or
utilized as the primary or supplemental heat source and in all dwelling
units with an attached garage, where the garage contains, is adjoining
to, adjacent to, contiguous with, and/or in the immediate vicinity
of a sleeping area.
705.2 Installation and Location of Detectors. An approved carbon
monoxide (CO) detector shall be installed in the following locations:
In all dwelling units where a fossil fuel or solid fuel appliance
is maintained or utilized as the primary or supplemental heat source,
a carbon monoxide (CO) detector shall be installed where the fuel-burning
appliance is being used.
In all dwelling units with an attached garage where the garage
contains, is adjoining to, adjacent to, contiguous with, and/or
in the immediate vicinity of a sleeping area, a carbon monoxide
(CO) detector shall be installed in the immediate vicinity of any
such sleeping areas, unless otherwise approved by the City.
Additional carbon monoxide (CO) detector shall be installed in
each location as required by the code inspector. It is the responsibility
of the owner of each dwelling unit or garage to obtain the advice
and approval of such inspector.
705.3 Detectors. Approved detectors must have h UL ratings or equivalent
rating.
705.4 Additional responsibilities. It shall be the responsibility
of the property owner to provide functioning carbon monoxide alarms,
per the requirements of this Section. Removal of the battery or
power source from a carbon monoxide alarm, making the detector inoperable,
is a violation of this Section.
(Ord. 4340 – Passed 9/20/05; Ord. 4419 – Passed 3/6/07;
Ord. 2010-27 – Passed 12/7/10.)
|